Alpha Essentials Page 111 Tray Cable

Alpha Wire www.alphawire.com 1-800-52 ALPHA Specifications subject to change. For complete specifications and availability, visit www.alphawire.com. 111 Tray Cable 600 V Unshielded, Multiconductor, PVC/Nylon, PVC UL TC Operating Temperature -25C to +90C Conductor Color Coding Chart D Materials Stranded tinned copper conductors PVC/nylon insulation Black PVC jacket Features UL Sunlight Resistant UL Direct Burial Availability 100 ft (30.5 m) 500 ft (152 m) 1000 ft (305 m) Bulk, cut to length (Minimums may apply) 18 AWG (0.96 mm 2 ) Stranding: 19/30 (19 x 0.25 mm) Insulation thickness: 0.016 (0.41 mm) PVC/0.005 (0.13 mm) nylon Part No. Conductors Nominal Diameter Jacket Thickness Inch mm Inch mm M39056 2 0.283 7.19 0.048 1.22 16 AWG (1.32 mm 2 ) Stranding: 19/0.0117 (19 x 0.30 mm) Insulation thickness: 0.016 (0.41 mm) PVC/0.005 (0.13 mm) nylon Part No. Conductors Nominal Diameter Jacket Thickness Inch mm Inch mm M39057 2 0.301 7.65 0.048 1.22 14 AWG (2.08 mm 2 ) Stranding: 41/30 (41 x 0.25 mm) Insulation thickness: 0.022 (0.56 mm) PVC/0.005 (0.13 mm) nylon Part No. Conductors Nominal Diameter Jacket Thickness Inch mm Inch mm M39058 2 0.355 9.02 0.048 1.22 12 AWG (3.29 mm 2 ) Stranding: 65/30 (65 x 0.25 mm) Insulation thickness: 0.022 (0.56 mm) PVC/0.005 (0.13 mm) nylon Part No. Conductors Nominal Diameter Jacket Thickness Inch mm Inch mm M39059 2 0.393 9.98 0.048 1.22