Alpha Essentials Page 154 Data and Bus Cable

Alpha Wire www.alphawire.com 1-800-52 ALPHA Specifications subject to change. For complete specifications and availability, visit www.alphawire.com. 154 Data and Bus Cable 300 V Power and Data, Class 2, ODVA Thick and Thin Trunks Device Net UL CMG UL PLTC-ER (Thick) UL CL2 (Thin) CSA CMG FT4 CSA AWM I/II A/B FT4 Operating Temperature -20C to +75C (static) 0C to +80C (dynamic) Conductor Color Coding Black-Red power Blue-White data Materials Tinned copper conductors Each pair individually foil shielded PVC insulation (power pair) Foam HDPE insulation (data pair) 65% tinned copper braid overall Slate PVC jacket Features Oil resistant UL Sunlight Resistant 120-ohm nominal impedance (data pair) Compliant with Allen-Bradley part numbers 1485 CPI-A and 1485 CPI-C Availability 100 ft (30.5 m) 500 ft (152 m) 1000 ft (305 m) Part No. Type Pairs Nominal Diameter Inch mm 6451 Thick 1 Power: 15 AWG (1.75 mm 2 ), 19/0.0135 (19 x 0.35 mm) stranding 1 Data: 18 AWG (0.96 mm 2 ), 19/30 (19 x 0.25 mm) stranding 0.480 12.19 6452 Thin 1 Power: 22 AWG (0.38 mm 2 ), 19/34 (19 x 0.16 mm) stranding 1 Data: 24 AWG (0.24 mm 2 ), 19/36 (19 x 0.13 mm) stranding 0.280 7.11 FIT Tubing Recommendations FIT-221: General-purpose, cross-linked polyolefin FIT-321: Medium-wall, adhesive- lined, cross-linked polyolefin