Alpha Wire www.alphawire.com 1-800-52 ALPHA Specifications subject to change. For complete specifications and availability, visit www.alphawire.com. 88 Communication and Control 300 V Individually Foil Shielded Pairs or Overall Foil Shielded, Multipair, Foam PP, PVC Individually Foil Shielded Pairs 24 AWG (0.23 mm 2 ) Stranding: 7/32 (7 x 0.20 mm) Insulation thickness: 0.023 (0.58) Part No. Pairs Nominal Diameter Jacket Thickness AWM Inch mm Inch mm 6073C 3 0.374 9.50 0.048 1.22 2493 6076C 6 0.483 12.27 0.048 1.22 2493 6079C 9 0.597 15.16 0.065 1.65 2493 Characteristic impedance: 115 ohms Mutual capacitance: 12 pF/ft (41 pF/m) Overall Foil Shield 22 AWG (0.32 mm 2 ) Stranding: Solid Insulation thickness: 0.023 (0.58) Part No. Pairs Nominal Diameter Jacket Thickness AWM Inch mm Inch mm 6072C* 2 0.42 9.50 0.035 0.89 2668 Characteristic impedance: 150 ohms Mutual capacitance: 8.8 pF/ft (28.9 pF/m) UL AWM 2493, 2668 VW-1 UL CM CSA CMG FT4 Operating Temperature -20C to +75C (CM) -20C to +60 (AWM, CMG) Conductor Color Coding Chart K Materials Solid or stranded tinned copper conductors Foam polypropylene insulation Individual aluminum/polyester foil shield, 25% overlap min. Foil facing inward Stranded tinned copper drain wire, 24 AWG Slate PVC jacket (unless otherwise noted) Availability 100 ft (30.5 m) 500 ft (152 m) 1000 ft (305 m) *Black jacket.