Ecogen Wire And Cable Page 32 EcoFlex

Alpha Wire www.alphawire.com 1-800-52 ALPHA Specifications subject to change. For complete specifications and availability, visit www.alphawire.com. 32 UL AWM 21819 (600 V, 105C) UL AWM 21492 (300 V, 80C) UL VW-1 CSA I/II A/B FT1 Temperature Range -40C to + 80C Conductor Color Coding Chart D Materials Tinned copper conductors mPPE insulation mPPE jacket, slate Bend Radius Unshielded: 5x static, 5x flexing Shielded: 6x static, 8x flexing Properties Zero halogen Specific gravity: 1.03 100% recyclable Low outgassing Suitable for use in NFPA 79 applications IEC 60332-2 Flame Behavior Availability 100 ft (30.5 m) 1000 ft (305 m) Bulk, cut to length FIT Tubing Recommendations FIT-221L: Low smoke zero halogen FIT Spiral Wrap: Zero-halogen wrap simplifies wire harnessing, cabling, and bundling EcoFlex Cable 600 V Unshielded, Multiconductor 14 AWG (2.08 mm 2 ) Stranding: 41/30 (41 x 0.25 mm) Insulation thickness: 0.011 (0.28 mm) Jacket thickness: 0.035 (0.81 mm) Part Number Conductors Nominal Diameter Inch mm 79028 2 0.266 6.76 79029 3 0.281 7.14 79030 4 0.307 7.80 79031 5 0.335 8.51 79032 7 0.364 9.25 79033 9 0.459 11.66 79034 12 0.473 12.01 79035 18 0.556 14.12 10 AWG (5.32 mm 2 ) Stranding: 105/30 (105 x 0.25 mm) Insulation thickness: 0.012 (0.30 mm) Jacket thickness: 0.035 (0.81 mm) Part Number Conductors Nominal Diameter Inch mm 79041 3 0.380 9.65 79042 4 0.423 10.74 79043 5 0.465 11.81 12 AWG (3.29 mm 2 ) Stranding: 65/30 (65 x 0.25 mm) Insulation thickness: 0.012 (0.30 mm) Jacket thickness: 0.035 (0.81 mm) Part Number Conductors Nominal Diameter Inch mm 79037 3 0.326 8.28 79038 4 0.358 9.09 79039 5 0.392 9.96 79040 7 0.428 10.87