Ecogen Wire And Cable Page 7 EcoCable

Alpha Wire www.alphawire.com 1-800-52 ALPHA Specifications subject to change. For complete specifications and availability, visit www.alphawire.com. 7 22 AWG (0.35 mm 2 ) Stranding: 7/30 (7 x 0.25 mm) Insulation thickness: 0.010 (0.25 mm) Jacket thickness: 0.032 (0.81 mm) Part Number Conductors Nominal Diameter Inch mm 77007 2 0.168 4.27 77008 4 0.189 4.80 77009 5 0.204 5.18 77010 7 0.219 5.56 77011 9 0.251 6.38 77012 19 0.318 8.08 UL AWM 21915 CSA AWM I/II A/B FT2 Operating Temperature -50C to 105C Conductor Color Coding Chart E Materials Stranded tin-plated copper conductors mPPE insulation mPPE jacket, slate Properties Zero halogen Specific gravity: 1.03 100% recyclable Low outgassing Suitable for use in NFPA 79 applications Availability 100 ft (30.5 m) 1000 ft (305 m) Bulk, cut to length FIT Tubing Recommendations FIT-221L: Low smoke zero halogen FIT Spiral Wrap: Zero-halogen wrap simplifies wire harnessing, cabling, and bundling EcoCable 600 V Unshielded, Multiconductor 18 AWG (0.81 mm 2 ) Stranding: 16/30 (16 x 0.25 mm) Insulation thickness: 0.010 (0.25 mm) Jacket thickness: 0.032 (0.81 mm) Part Number Conductors Nominal Diameter Inch mm 77020 2 0.202 5.13 77021 3 0.213 5.41 77022 4 0.230 5.84 77023 5 0.250 6.35 77024 7 0.271 6.88 77025 9 0.313 7.95 77026 12 0.346 8.79 77027 15 0.377 9.58 77028 19 0.404 10.26 77029 25 0.470 11.94 20 AWG (0.56 mm 2 ) Stranding: 7/28 (7 x 0.32 mm) Insulation thickness: 0.010 (0.25 mm) Jacket thickness: 0.032 (0.81 mm) Part Number Conductors Nominal Diameter Inch mm 77056 2 0.184 4.67 77013 3 0.193 4.90 77014 4 0.209 5.31 77015 9 0.280 7.11 77016 12 0.309 7.85 77017 15 0.336 8.53 77018 19 0.358 9.09 77019 25 0.416 10.57